On the PCB in the pump, under the cap, is a 16-position switch to select the working
mode. This working mode determines how the pump reacts on sensor, button, RS232 signals
etcetra.
Each working mode is designed for a specific function.
You must select a working mode (only once) to let the working correspond with your
application.
| Working mode 0 = not used (for older
pumps this is a function to callibrate, but now callibration can be done much easier with
the supplied Monitor Program)
|
to
calibrate all sensors |
|
| model #905,910,915
and #805,810,815,855 Working mode 1
= straight pumping mode (no sensors)

|
deliver
LN2 as controlled by pumpbutton or external signal |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping on
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump |
| model #905,910,915 and #805,810,815,855 Working mode 2 = FILL control (1 sensor)

|
fill
various vessels, one after the other |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping on as long as sensor is warm, stop pumping when sensor is cold, return to sleep
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump |
| model #905,910,915 and #805,810,815,855 Working mode 3 = automatic FILL control with timer (1 sensor)

|
fill
application repeatedly with timer |
Button on pump allows operator to toggle between Active and Sleep Active
= start pumping on as long as sensor is warm, stop pumping when sensor is cold, repeat
after 1* hour
Sleep = stop Active, reset timer, set internal freeze protector ON to prevent ice
clogging in risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump
*NOTE: timer setting can be changed in display screen on a computer in steps of 1
minute between 5 minutes minimum and 7 days maximum
*NOTE: for this appication the EXTRA sensor connection must be used |
| model #905,910,915 and #805,810,815,855 Working mode 4 = 1-point level control (1 sensor)

|
maintain
LN2 level at sensor height |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping as long as sensor is warm, not pumping when sensor is cold
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump |
| model #905,910,915 and #805,810,815,855 Working mode 5 = 2-point level control (2 sensors)

|
maintain
LN2 level between 2 sensors |
Button on pump allows operator to toggle between Active and Sleep Active
= start pumping when low sensor is warm, not pumping when high sensor is cold
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump |
| model #905,910,915 and #805,810,815,855 Working mode 6 = 1-point level flow control (1 sensor)

|
maintain LN2 level at sensor
height, keep dripping to hold that level |
Button on pump allows operator to toggle between Standby and Sleep Standby
= pumping as long as sensor is warm, slower pumping when sensor is almost cold, stop
pumping when sensor is completely cold
Sleep = stop Standby, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in STANDBY mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump |
| Working mode 7
for future use |
|
|
| model
#910,915 and #810,815 Working mode 8
= local temperature control (1 sensors)

|
deliver LN2 as controlled by temperature setpoint on pump, or external
analog 0-5V signal |
Button on pump allows operator to toggle between Active and
Sleep Active = pumping as long as sensor is above- , not- or soft-pumping when sensor is
below temperature setpoint (*1) pumpingflow is depending of the speed of the temperature
changements. (P.I.D.)
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump
(*1)temperature setpoint is depending on jumper setting JP7
(*2)range is depending on jumper setting JP6JP6 open = range -200 to +70 degrees
CelciusJP6 closed = range +/- 30 degrees relative to potmeter P1 on print |
| model #910,915 and
#810,815 Working mode 9 = FLOW
control by external signal (no sensors)

|
deliver
LN2 as controlled by external analog 0-5V signal |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping with flow as set by external 0-5 volt signal (0 volt = stop pumping)(*1)
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
Maximum FLOWRATE is set by potmeter on pump
(*1) external analog signal on pin 10 of 25 p D connector delivers a flow depending on
the setting of the flowpotmeter on the pump 0 - 5 Volt deliveres 0 - 100% of the
adjustment of the FlowPotmeter on the pump. |
| model #910,915 and
#810,815 Working mode A = remote
temperature control (1 sensor)

|
deliver
LN2 as controlled by external analog 0-5V signal(s) |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping as long as sensor is above- , not- or soft-pumping when sensor is below
temperature setpoint(*1) pumpingflow is depending of the speed of the temperature
changements. (P.I.D.) Active = when pumping, use maximum flow as set by external 0-5 volt
signal (0 volt = stop pumping)(*3)
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
Maximum FLOWRATE is set by potmeter on pump
(*1)temperature setpoint is depending on jumper setting JP7
(*2)range is depending on jumper setting JP6JP6 open = range -200 to +70 degrees
CelciusJP6 closed = range +/- 30 degrees relative to potmeter P1 on print
(*3) external analog signal on pin 10 of 25 p D connector deliveres a flow depending on
the setting of the flowpotmeter on the pump 0 - 5 Volt deliveres 0 - 100% of the
adjustment of the FlowPotmeter on the pump.
(*4) external analog signal for temperature setpoint 0 - 5 Volt gives a setpoint from
-200 to +70 degrees Celcius acording PT100 characteristics |
| model #910,915 and
#810,815 Working mode B = FLOW
control by external signal (and 1 sensor)

|
deliver
LN2 as controlled by external analog 0-5V signal and 1 sensor |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping with flow as set by external 0-5 volt signal (0 volt = stop pumping)(*1) pumping
as long as sensor is warm, not pumping when sensor is cold
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connectorMaximum
maximum FLOWRATE is set by potmeter on pump
(*1) external analog signal on pin 10 of 25 p D connector deliveres a flow depending on
the setting of the flowpotmeter on the pump 0 - 5 Volt deliveres 0 - 100% of the
adjustment of the FlowPotmeter on the pump. |
| model #910,915 and
#810,815 Working mode C = local
temperature control (2 sensors)

|
deliver
LN2 as controlled by temperature setpoint on pump, or external analog 0-5V signal, and
extra sensor for STOP |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping as long as sensor is above- , not- or soft-pumping when sensor is below
temperature setpoint (*1). Pumping as long as extra sensor is warm, not pumping when extra
sensor is cold. Pumping flow is depending of the speed of the temperature
changements. (P.I.D.)
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
FLOWRATE is set by potmeter on pump
(*1)temperature setpoint is depending on jumper setting JP7
(*2)range is depending on jumper setting JP6. JP6 open = range -200 to +70 degrees
Celcius. JP6 closed = range +/- 30 degrees relative to potmeter P1 on print |
| Working mode D
= for future use |
|
|
| model #915 and #815 Working mode E = remote temperature control (1 sensor controls
pumping, additional sensor optional for measurement)

|
deliver
LN2 as controlled by external RS232 signals and 1 sensor |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping as long as sensor is above- , not- or soft-pumping when sensor is below
temperature setpoint as set by RS232 signal
pumpingflow is depending of the speed of the temperature changements. (P.I.D.)
input RS232 signal for temperature setpoint(*1)
input RS232 signal for flow(*2)
input RS232 signal for pumping status SLEEP, ACTIVE
output RS232 signal from pump status
output RS232 signal from both sensors
output RS232 signal from maximum flow setting on pump
output RS232 signal from setpoint
output RS232 signal from pressure, LED status, Beeper
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
Maximum FLOWRATE is set by potmeter on pump
(*1) input RS232 signal for temperature setpoint -200 to 50 gives a setpoint from -200
to +50 degrees Celcius.
(*2) input RS232 signal for flow deliveres a flow depending on the setting of the
flowpotmeter on the pump. 0 - 100 deliveres 0 - 100% of the adjustment of the FlowPotmeter
on the pump. |
model
#915 and #815
Working mode F = remote temperature control (2
sensors optional for measurement)

|
deliver
LN2 as controlled by external RS232 signals |
Button on pump allows operator to toggle between Active and Sleep Active
= pumping as dictated by RS232 signals
input RS232 signal for flow (*1)
input RS232 signal for pumping status SLEEP, ACTIVE, PUMPING
output RS232 signal from pump status
output RS232 signal from both sensors
output RS232 signal from maximum flow setting on pump
output RS232 signal from pressure, LED status, Beeper
Sleep = stop Active, set internal freeze protector ON to prevent ice clogging in
risepipe
pump can be put in ACTIVE mode with TTL signal or +24V signal on 25D connector
pump can be put in SLEEP mode with TTL signal or +24V signal on other pin of 25D
connector
(Maximum FLOWRATE is NOT set by potmeter on pump)
(*1) input RS232 signal for flow 0 - 250 deliveres a flow from 0 to 250 mBar. |
| all models
#9xx and #8xx
25p Dconn pins |
|
1=14 AC1 AC or DC 12 to 24 Volts
Power supply (min. 4 A.)
13=25 AC2
AC or DC 12 to 24 Volts Power supply (min. 4 A.)
17=18=19=20 system ground
8 RXD serial connection
9 TXD serial connection
4 TTL_1 input, 0 or 5 Volt, 0 Volt = switch pump to
SLEEP
5 TTL_2 input, 0 or 5 Volt, 0 Volt = switch pump to
ACTIVE
10 ext. flow input, analog 0-5 Volt
11 ext. temp setpoint input, analog 0-5 Volt
6 ext. EXTRA sensor input ( PT100 element ) to
ground
7 ext. MAIN sensor input ( PT100 element ) to
ground
15 opt1C optocoupler input 1 neg.
2 opt1A optocoupler input 1 pos. : 0 or 5-24 Volt
input. 5-24 V. to switch pump to ACTIVE
16 opt2C optocoupler input 2 neg.
3 opt2A optocoupler input 2 pos. : 0 or 5-24 Volt
input. 5-24 V. to switch pump to SLEEP
(*) connect C to ground and supply positive signal to A to switch
(*) OR, connect A to ground to use negative signal on C to switch
12 output TTL 5 Volt external heater LOW = active
(*)
21 optEXH1E optocoupler output emitter for external
heater (*)
22 optEXH1C optocoupler output collector for
external heater (*)
23 optAL2E optocoupler output emitter ALARM
24 optAL2C optocoupler output collector ALARM
(*) connect E = emitter to ground to switch a positive signal
(*) OR, connect C = collector to ground to switch a negative signal |
| |
|
|